1,3,3,3-Tetrafluoropropene
1,3,3,3-Tetrafluoropropene (HFO-1234ze(E)) is a hydrofluoroolefin. It was developed as a "fourth generation" refrigerant to replace fluids as R-134a and as a blowing agent for foam and aerosol applications.[4] The use of R-134a is being phased out because of its high global-warming potential. HFO-1234ze(E) has zero ozone-depletion potential (ODP=0), a very low global-warming potential (GWP < 1 ), even lower than CO2, and it is classified by ANSI/ASHRAE[5] as class A2L refrigerant (lower flammability and lower toxicity). [6]
Names | |
---|---|
IUPAC name
(1E)-1,3,3,3-Tetrafluoro-1-propene | |
Other names
HFO-1234ze; trans-1,3,3,3-Tetrafluoro-1-propene; 1,3,3,3-Tetrafluoropropylene; 1,3,3,3-Tetrafluoroprop-1-ene | |
Identifiers | |
3D model (JSmol) |
|
ChemSpider | |
ECHA InfoCard | 100.214.545 |
EC Number |
|
PubChem CID |
|
CompTox Dashboard (EPA) |
|
| |
| |
Properties | |
C3H2F4 | |
Molar mass | 114.043 g·mol−1 |
Appearance | Colorless gas[3] |
Boiling point | −19 °C (−2 °F; 254 K)[3] |
0.373 g/L[3] | |
Vapor pressure | 703 kPa at 310 K |
Except where otherwise noted, data are given for materials in their standard state (at 25 °C [77 °F], 100 kPa). | |
Infobox references | |
Uses
The increasing concerns about global warming and the related possible undesirable climate effects have led to an increasing agreement in developed countries for the reduction of greenhouse gas emissions. Given the relatively high global warming potential (GWP) of most of the hydro-fluoro-carbons (HFCs), several actions are ongoing in different countries to reduce the use of these fluids. For example, the European Union’s recent F-Gas regulation [7] specifies the mandatory GWP values of the refrigerants to be used as working fluids in almost all air conditioners and refrigeration machines beginning in 2020.[8]
Several types of possible replacement candidates have been proposed so far, both synthetic and natural. Among the synthetic options, hydro-fluoro-olefins (HFOs) are the ones appearing most promising thus far.
HFO-1234ze(E) has been adopted as working fluid in chillers, heat pumps, and supermarket refrigeration systems.[9][10][11]
It has been demonstrated that HFO-1234ze(E) can not be considered as a drop-in replacement of HFC-134a. In fact, from a thermodynamic point-of-view, it can be stated that:
– The theoretical coefficients of performance of HFO-1234ze(E) is slightly lower than HFC-134a one;
– HFO-1234ze(E) has a different volumetric cooling capacity when compared to HFC-134a.
– HFO-1234ze(E) has saturation pressure drops higher than HFC-134a during two-phase heat transfer under the constraint of achieving the same heat transfer coefficient.[12]
So, from a technological point-of-view, modifications to the condenser and evaporator designs and to compressor displacement are needed to achieve the same cooling capacity and energetic performance of HFC-134a.[8]
See also
- 2,3,3,3-Tetrafluoropropene (HFO-1234yf)
References
- MSDS for HFO-1234ze
- Honeywell Sells Novel Low-Global-Warming Blowing Agent To European Customers, Honeywell press release, Oct. 7, 2008
- ANSI/ASHRAE Standard 34, 2010. Designation and Safety Classification of Refrigerants.
- https://www.honeywell-refrigerants.com/india/?document=solstice-ze-hfo-1234ze-brochure-2012&download=1
- (Regulation [EC] No 517/2014)
- Giulia Righetti, Claudio Zilio, Simone Mancin & Giovanni A. Longo (2016): A review on in-tube two-phase heat transfer of hydro-fluoro-olefines refrigerants, Science and Technology for the Built Environment, DOI:10.1080/23744731.2016.1229528
- Longo, Giovanni A.; Zilio, Claudio; Righetti, Giulia; Brown, J. Steven (2014). "Condensation of the low GWP refrigerant HFO1234ze(E) inside a Brazed Plate Heat Exchanger". International Journal of Refrigeration. 38: 250–259. doi:10.1016/j.ijrefrig.2013.08.013.
- Longo, Giovanni A.; Mancin, Simone; Righetti, Giulia; Zilio, Claudio (2016). "HFO1234ze(E) vaporisation inside a Brazed Plate Heat Exchanger (BPHE): Comparison with HFC134a and HFO1234yf". International Journal of Refrigeration. 67: 125–133. doi:10.1016/j.ijrefrig.2016.04.002.
- Longo, Giovanni A.; Mancin, Simone; Righetti, Giulia; Zilio, Claudio (2016). "Saturated flow boiling of HFC134a and its low GWP substitute HFO1234ze(E) inside a 4 mm horizontal smooth tube". International Journal of Refrigeration. 64: 32–39. doi:10.1016/j.ijrefrig.2016.01.015.
- Brown, J.S., C. Zilio, R. Brignoli, and A. Cavallini. 2013. Heat transfer and pressure drop penalization terms (exergy losses) during flow boiling of refrigerants. International Journal of Energy Research 37:1669–79.